GEKKO data logger is designed in a robust industrial design. It can be supplied using either the 2 pcs. lithium batteries or external voltage supply 12-30V DC.
GEKKO is equipped with 2 pcs. analog inputs which are 0/4-20mA or with 4 digital inputs, 2 of which can be configured as 0-10V inputs or as pulse inputs for counter. In addition, RS485 MODBUS communication with external devices is possible.
GEKKO is designed for use in wastewater and water supply applications and can collect data and log signals of several different types with the help of external equipment, e.g. used for H2S detection, level measurement, overflow registrations and for registration of precipitation events.


Communication
GEKKO data logger can communicate via standard MODBUS TCP/IP or SMS commands. Communication takes place via 4G modem (2G, 3G and 4G) or Sigfox modem – both are mounted on their own print. Thus, communication can be changed to future form of communication without changing the entire data logger.
Communication to SCADA / SRO takes place through the program AcowaCore, which i.a. enables handling of an event-based logging function typically used in overflow registration. GEKKO has a USB interface for programming GEKKO or for downloading logs in data loggers.
- Specifications
- Inputs
- Item number
- Applications
- Documentation
SPECIFICATIONS | |
---|---|
Dimensions | L=186mm, W=156mm, H=60mm |
Weight | 620g without batteries |
Wire connection | 0.5–2,5 mm2 |
Vibration (sinusoidal) | 10-500Hz, 1G |
Free fall drop | 30 cm |
Enclosure class | IP67 |
Power supply | 12V DC – 30V DC |
Batteries | 2 x Lithium SAFT |
ENVIRONMENT | |
Humidity | Humidity 10% - 95% non-condensing air |
Operating temperature | -20°C to +50°C |
Storage temperatur | -20°C to +60°C |
Functional height | Max. 2000m above sea level |
Start-up time total | 20-120 sec. (depending on GSM network) |
Built-in power supply: | |
Output voltage | 15V DC |
Output current | Max. 100mA |
Tolerance | +/- 20% |
ANALOG INPUTS: | |
---|---|
Number of analog mA inputs | |
Electrically insulated | No |
Measuring range | 0/4–20mA |
Input impedance | Approx.100Ω |
Measurement accuracy | Better than 0,5% of FS |
Signal range | 0-24mA / 0–30V DC |
Cable/signal length | Max. 100m |
Digital inputs / AI 0-10V: | |
Number of digital inputs | 2 |
Electrically insulated | No |
Digital signal | Low < 5V / < 1mA High > 12V / > 4mA |
Analog signal measuring range | 0–10V DC |
Analog signal impedance | Approx. 20KΩ |
Measurement accuracy | Better than 1% of FS |
Signal range (min/max.) | 0–30V DC |
Cable/signal length | Max. 100m |
Item number | Description |
---|---|
1772-2204000 | GEKKO 4G. |
1772-2204100 | GEKKO SIGFOX. |
UHR-13Ah | Lithium SAFT 3,6V battery |
1717-0B24-C884G | Quad band antenna (2G, 3G, 4G) w angle connector |
Sigfox-U | 5 year SigFox subscription incl. creation on Sigfox back-end as well as invoice handling. |
The TurTle level sensor is very flexible and can be used in many different applications, such as:
- Pumping stations
- Sewage treatment plants
- Stormflow
- Level monitoring
- Rivers or streams
- Reservoir and tanks